国产波波社区精品视频_一本无码AV不卡在线播放观看_国产午夜精品一区不卡AV_久热国产精品_狠狠色婷婷久久一区二区三区_婷婷网色偷偷亚洲的天堂_花季传媒下载_久久极品免费视频最熱門最齊全電影!_无码国产精品午夜福利_在线观看国产欧美高清

EnglishGermany
PRODUCT.產(chǎn)品

Gas monitor unit- MWS 903

The multi-channel gas warning equipment ADOS 
MWS 903 continuously monitors the surrounding air and provides an early warning of dangerous, explosive and non-combustible gases and vapours.
It is possible to connect up to 8 gas transmitters 
(2- or 3-wire) to the unit.
  • 技術(shù)參數(shù)
  • 產(chǎn)品特點(diǎn)
  • 應(yīng)用領(lǐng)域
  • 資料下載
Examples of measurable gases
Gas Formula
Acetylene C2H2
Ether C4H10O
Alcohol e.g. C2H6O
Ammonia NH3
Petrol
 
Butane C4H10
Chloroform CHCl3
Hydrogen chloride HCl
Helium He
Carbon dioxide CO2
Carbon monoxide CO
Methane (natural gas) CH4
Neon Ne
Propane C3H8
Oxygen O2
Carbon tetrachloride CCl4
Toluene C7H8
Hydrogen H2
Xylene C8H10




Technical Data
Sensor inputs: 8 two-or-three-wire sensors
(e.g. LCTR 903) with current interface,
4–20 mA
Sensor supply: 24 V= / 200 mA
Ranges: CO 0-300 ppm
NO2 0-30 ppm
CH4 0-100 % UEG
CO2 0-10 Vol %
other ranges on request
Ambient temperature: -10 °C to +40 °C
Digital inputs: 1 input for siren cancel
Digital outputs: max. 12 alarms
1 fault relay
1 siren relay
Warning banner relay
All outputs have floating change-over contacts, max. rating 250 V / 4 A
Standard output signals: Analog output 4–20 mA serial interface RS 232
Mains connection: 230 V / 50 Hz
115 V / 60 Hz (optional)
24 V / DC (optional)
Dimensions (WxHxD): 240 x 160 x 90 mm
Weight: approx. 2 kg
Protection type: IP 54 according to DIN 40050

  • 6-section keybord and illuminated 4-line LC-Display for indicating actual values, half-hourly average values and fault messages, all clear text encoded
  • Ready, fault and gas warning display
  • Menu-assisted settings for the equipment parameters, via 6-section keyboard
  • Two alarm thresholds for each sensor, independently adjustable from 5 % to 100 % of the measurement range; facility for forming half-hourly average value
  • A maximum of 12 floating alarm outputs for controlling extra warning and control devices
  • Floating change-over contacts for fault, siren and warning banners
  • Serial interface output, RS 232 for connecting a printer or PC
  • Plastic, wall-mounted housing (IP 54)
  • 4–20 mA interface
  • Plastic, wall-mounted housing
  • High operational reliability
  • Low current consumption
  • Easy installation
  • USP unit available
  • Heating systems
  • Garages and tunnels
  • Liquid gas storage rooms
  • Laboratories
  • Cold-storage houses
  • Plastic processing plants
  • Chemical industries
  • Paint manufacturing plants
  • Concentration measurement of O2
  • and many more
版權(quán)所有 ? 2004- 深圳市昂為電子有限公司 ONUEE / ONWARDS(HK) Ltd. All rights reserved. 粵ICP備09176163號(hào)/